100KW Diesel Generator Set
The world's top brand engine and the most advanced fuel high-pressure common rail technology (for some models) are adopted to achieve the optimal fuel consumption.

O
Through 3D construction and finite element analysis simulation software, the unit can carry out load bearing and vibration calculation and multiple long-term operation tests, effectively reduce the unit operation vibration, and ensure stable and reliable operation.
The advanced outdoor structure design have been repeatedly tested and verified to ensure the rainproof anti-corrosion performance and reliable operation in harsh environments such as high temperature, high humidity, sandstorm and dust, with the highest level of C5- industrial anti-corrosion.
|
|
|
|
|
|
|
|
|
|
1 |
1 |
5 |
2 |
||||
|
2 |
1 |
6 |
1 |
||||
|
3 |
1 |
7 |
1 |
||||
|
4 |
1 |
8 |
1 |
|
|
|
|
|
Phase voltage, line voltage, current, frequency, phase sequence, active power, reactive power, apparent power, power factor, cumulative generating power, speed, oil pressure, cooling water temperature, unit running time, cumulative start-up times, battery voltage, etc. |
|
|
Overspeed, underspeed, overvoltage, undervoltage, overfrequency, underfrequency, over-current, over-power, low oil pressure, high water temperature, low battery power, charging failure, etc. |
Cool tags: 100kw-60hz-400v trailer type diesel generator set, China 100kw-60hz-400v trailer type diesel generator set manufacturers, suppliers, factory
|
YC-E125GF2 |
|
|
100KW |
|
|
1800r/min |
|
|
400V |
|
|
180.4A |
|
|
60HZ |
|
| 0.8(lagging) | |
|
95.9% |
|
| Less than or equal to 192g/kwh | |
| Less than or equal to 82Lp dB(A) | |
|
1650kg |
|
|
YC4D180-D33 |
|
|
103kW |
|
|
1800r/min |
|
|
4 |
|
|
108mm × 115mm |
|
|
4.214L |
|
|
17.5:1 |
|
|
KAL274B2 |
|
| 3 and Y shape | |
| IP23 | |
| H | |
| Generating-set Performance | |
| 95-105% | |
| ±1% | |
| Transient voltage deviation(100% load sudden reduce) | Less than or equal to +20% |
| Less than or equal to -15% | |
| Voltage stabilization time(100% load sudden reduce) | Less than or equal to 3s |
| Less than or equal to 3s | |
| Less than or equal to ±1% | |
| Steady-state frequency regulation | Less than or equal to ±0.5% |
| ±0.5% | |
| Transient frequency deviation(100% load sudden reduce) | Less than or equal to +10% |
| Less than or equal to -7% | |
| Frequency Recovery Time(100% load sudden reduce) | Less than or equal to 3s |
| Less than or equal to 3s | |